40 KVA Tata Powerlux Generator
- Engines are tested as per IS 10000 standards
- Superior Quality alternators are used confirming to IS13364, IS4722 & BS5000 standards
- Technologically advanced control panels with deep sea/ Procom controller
- Heavy, Robust and sound efficient DG gets confirming to CPCB-II norms & rule 95 of environment protection of GSR no of 771 (E) & GSR 232 (E)
Description
40 KVA TATA Silent Diesel Generator, 3 Phase
Duty | Prime |
Starting System | 12V |
Model | 4SP |
No. of Cylinders | 4 |
Aspiration | Turbocharger Intercooler |
Lube oil change period | 500 |
Class of Insulation | Class H |
Voltage (V) | 215 V / 415 V |
Power Factor | 0.8 (lagging) |
Maximum unbalanced load across phases | Up to 25% |
Power Rating kVA | 40 |
Power Rating kWe | 32 |
Current | 174 / 55 Amp |
RPM / Frequency | 1500 RPM / 50 Hz |
DG Set Noise at 1 meter | < 75 dBA |
Rated Power (kW) | 55 |
Horse Power | 74 |
Performance class | ISO 8528 |
Governing class | G3 |
Displacement | 2956 |
Bore X Stroke | 97 x 100 |
Rated Speed | 1500 |
Ambient Temperature Range | -10 to 50 deg C |
Fuel System | CRDI |
Total lubrication system capacity (litre) | 8.3 |
Total coolant capacity including engine & radiator (litre) | 12 |
DEF Capacity (litre) | NA |
Fuel | High Speed Diesel |
Lube oil | CK4 15W40 |
Enclosure type | IP23 |
Voltage regulation | +/-1% |
Other Essentials:
- Engines are tested as per IS 10000 standards
- Superior Quality alternators are used confirming to IS13364, IS4722 & BS5000 standards
- Technologically advanced control panels with deep sea/ Procom controller
- Heavy, Robust and sound efficient DG gets confirming to CPCB-II norms & rule 95 of environment protection of GSR no of 771 (E) & GSR 232 (E)
How to Calculate Load:
- Put on only those equipments which you want to run on the Powerlux Silent Generator.
- Go near the distribution box where you’ll find four colored cables; Red, Yellow, Blue & Black.
- Put the clamp meter around the Red, Yellow & Blue cable one by one and note down the ampere rating. Now add the numbers in case of single phase requirement or pick the highest in case of three phase requirement.
- Select your kVA from the above given ampere chart and see under which rating your requirement falls.
Note:
- After putting the clamp meter around the cable; turn off and on the heavy machines/equipments for better calculation. Also always select a rating 20% higher to your load for long term usage.
- All of the above silent genset range is made to perform at 1500 RPM
- Rated current output is at 100% load. 0.8 power factor
- Weight mentioned is approximate
- Product innovation is a continuous process; hence data given is subject to change without any prior notice.
- Detailed technical specification sheet separately available for each rating in soft copy